Blog · Application
Box detection on a conveyor
Count the boxes, ignore the guard rail behind them, and get the distance to every box over IO-Link.
The problem
Counting cartons requires controlling what enters the beam. Distance background suppression can ignore a rail beyond the set distance, but it does not identify object type: a person or another object closer to the sensor can still trigger the output. Position the sensor and protect the sensing path so only cartons cross it; verify the real carton and background response on site.
The station
- Sensor ifm O5D100, laser distance with background suppression, class 1 laser, port class A
- Master Turck TBEN-S2-4IOL, 4 ports, PROFINET, EtherNet/IP or Modbus TCP
- Port X1, 4.7 m route, 10 m cable. The C0 to C3 supply is not short-circuit proof (4 A per group), so protect V2 in the cabinet
The settings that matter
| Setting | Value | Why | Datasheet / IODD |
|---|---|---|---|
| Switching distance | 500 mm (raw 50 cm) | Any object within 500 mm triggers; the rail beyond is ignored | Measuring range 0.03 to 2 m on 90 % white; IODD SP1 5 to 200 cm |
| Output | normally open | 24 V while a box is in front | Two complementary outputs |
| Box gap | check on site | Gap ÷ belt speed must be longer than one switching cycle | Switching frequency 15 Hz |
The 2 m range is for white paper at 90 % remission. Brown cardboard reflects less, so check the switch point with your real boxes. Extraneous light on the object must stay under 8 klx.
Run it
02 31: 0x231 shifted right by four is 35 cm, and bit 0 is OUT1.What you get
The screenshots show the earlier example. The JSON, CSV and current HTML report below use the current Studio data. They are proposed settings, not a record of physical commissioning.
The commissioning file has every port: validation IDs, cycle time, data storage, and each parameter as ISDU index, subindex and raw value. This is port X1 from the real file, trimmed to the fields that matter:
{
"port": 1,
"mode": "iolink",
"tag": "B1",
"device": {
"part": "O5D100",
"vendor": "ifm electronic",
"vendor_id": 310,
"device_id": 372,
"iodd_file": "ifm-000174-20210526-IODD1.1.xml",
"bitrate": "COM2",
"validation": {
"recommended": "type_compatible",
"vendor_id": 310,
"device_id": 372,
"alternatives": [
"none",
"type_compatible",
"identical"
],
"serial_number": null
},
"data_storage": {
"recommended": "backup_restore",
"note": "Parameters are kept in the master so a replacement device is loaded automatically. Needs a device that supports data storage; check the IODD."
},
"cycle_time_ms": {
"device_min": 6.4,
"recommended": 6.4
},
"process_data": {
"in_bits": 16,
"in_bytes": 2,
"out_bits": 0,
"out_bytes": 0,
"in_layout": [
{
"name": "Distance",
"bit_offset": 4,
"bits": 12,
"gradient": 1,
"unit": "cm"
},
{
"name": "Switch state [OUT1]",
"bit_offset": 0,
"bits": 1,
"gradient": null,
"unit": null
}
]
},
"parameters": [
{
"key": "switch_point",
"name": "Switching distance",
"kind": "setting",
"unit": "mm",
"value": 500,
"entered": 500,
"note": null,
"index": 60,
"subindex": 1,
"datatype": "UIntegerT",
"bit_length": 16,
"raw": 50,
"raw_hex": "00 32",
"clamped": false,
"status": "ok"
},
{
"key": "output",
"name": "Output function",
"kind": "option",
"unit": "",
"value": "normally open",
"entered": null,
"note": null,
"index": 61,
"subindex": 1,
"datatype": "UIntegerT",
"bit_length": 8,
"raw": 0,
"raw_hex": "00",
"clamped": false,
"status": "ok"
}
]
}
}
Download: commissioning file (JSON) · CSV · current station report (HTML)