IO-Link station report: commissioning data, wiring and bill of materials
Open this station in the studio: iolinki.com/studio
No 3D view captured.
Filed library settings and port assignments pass the Studio checks. The physical and integration blockers above remain open.
| From | To | Device | Route, m | Order length | Check |
|---|---|---|---|---|---|
| MASTER X1 | T_SUPPLY | TA2105 | 6.4 | 10 m | ≤ 20 m |
| MASTER X2 | T_RETURN | TA2105 | 9.2 | 15 m | ≤ 20 m |
| MASTER X3 | LIQUID_POINT | KG5065 | 11.9 | 15 m | ≤ 20 m |
Route is the laid path in the 3D model; order length adds 20 % slack and rounds up to a stock length.
| Port | Device | Vendor / device ID | Cycle time | Process data | Input layout | Data storage |
|---|---|---|---|---|---|---|
| MASTER X1 IO-Link | TA2105 T_SUPPLY · ifm electronic | 310 / 377 type compatible | 2.3 ms min 2.3 ms · COM2 | 2 B in 0 B out 16 / 0 bit | Temperature bit 0-15, x0.1 °C | Backup + restore |
| MASTER X2 IO-Link | TA2105 T_RETURN · ifm electronic | 310 / 377 type compatible | 2.3 ms min 2.3 ms · COM2 | 2 B in 0 B out 16 / 0 bit | Temperature bit 0-15, x0.1 °C | Backup + restore |
| MASTER X3 IO-Link | KG5065 LIQUID_POINT · ifm electronic | 310 / 387 type compatible | 100.8 ms min 100.8 ms · COM1 | 2 B in 0 B out 16 / 0 bit | PDV1 bit 4-15, x1 BDC1 bit 0 | Backup + restore |
| MASTER X4 | Deactivated, no device wired | |||||
Validation is set to type compatible (vendor ID and device ID must match). Use identical only when the device serial number is read at commissioning. Bit offsets count from the least significant bit of the input process data.
| Master | Sensors draw | Master supplies | Per port | Result |
|---|---|---|---|---|
| MASTER TBEN-S2-4IOL | 120 mA | 4000 mA | X1 TA2105 50 mA X2 TA2105 50 mA X3 KG5065 20 mA | within limits |
| Port | Parameter | Value | ISDU index.sub | Raw | Hex | Type | Status |
|---|---|---|---|---|---|---|---|
| MASTER X1 T_SUPPLY | Analogue start point ASP2 | 0 °C | 630.0 | 0 | 00 00 | IntegerT | ok |
| MASTER X1 T_SUPPLY | Analogue end point AEP2 | 60 °C | 631.0 | 600 | 02 58 | IntegerT | ok |
| MASTER X2 T_RETURN | Analogue start point ASP2 | 0 °C | 630.0 | 0 | 00 00 | IntegerT | ok |
| MASTER X2 T_RETURN | Analogue end point AEP2 | 60 °C | 631.0 | 600 | 02 58 | IntegerT | ok |
| MASTER X3 LIQUID_POINT | Hysteresis | 5 % of sensing range | - | - | - | - | no index |
| MASTER X3 LIQUID_POINT | Output function | normally open | 61.1 | 0 | 00 | UIntegerT | ok |
Raw = round((value - offset) / gradient). Prepare only the verified parameter rows for the master's ISDU function block. Do not write missing or unscaled raw values; read back all qualified writes at commissioning. Values for inductive sensors are already converted to the steel-equivalent switching distance.
| Qty | Kind | Vendor | Part | Vendor / device ID |
|---|---|---|---|---|
| 1 | master | Turck | TBEN-S2-4IOL | |
| 2 | sensor | ifm electronic | TA2105 | 310 / 377 |
| 1 | sensor | ifm electronic | KG5065 | 310 / 387 |
| 1 | cable | M12 A-coded 3/4-pole cable, 10 m | ||
| 2 | cable | M12 A-coded 3/4-pole cable, 15 m |
| Commissioned by | Date |
|---|