  "status": "engineering preparation only",
  "coverage": "partial: 3 of 5 proposed measurement points",
  "written_to_sensor": false,
  "physical_acceptance": "not performed",
  "installation": "not performed",
  "commissioning": "not performed",
  "unexported_candidates": [
    "SU6030",
    "PN7094"
  ],
  "temperature_settings": "0–60 °C analogue scaling only; not IO-Link alarms or approved coolant operating limits",
  "kg_setting": "5% hysteresis is an illustrative Studio value, not a factory setting or qualified teach result; raw write remains unavailable",
  "geometry": "Generic pipe runs and cabinet only; LIQUID_POINT is a proposed tray position without validated tray geometry. No CDU, rack, hydraulic or thermal model.",
  "blockers": [
    "KG5065 hysteresis has no verified ISDU scale; do not write the displayed percentage as raw.",
    "Qualify KG5065 with actual coolant, tray wall thickness/material, stand-off, condensation and deposits; test dry/wet teach and missed collection paths.",
    "Validate TA2105 wetted materials, adapter, immersion, mechanical installation and temperature response against the actual loop.",
    "Flow and pressure are outside the export catalog; five points exceed the four-port baseline and require another master or an eight-port selection.",
    "Commission master protocol ownership, process-data register mapping, byte order, freshness, watchdog and local controls before any BMS integration.",
    "Physical installation, device writes/readback, alarm settings and site acceptance remain outstanding."
  ]
}